产品分类
您现在的位置:首页>技术文章> Schneider驱动器LTMR100CFM数据
Schneider驱动器LTMR100CFM数据
  • 发布日期:2023-09-15 浏览次数:230
    • Schneider 驱动器LTMR100CFM

      TeSys T是一种电机管理系统,当与短路保护和接触器一起使用时,它提供完整的电机监控、控制和保护。它管理最关键的流程,同时减少停机时间,提高生产力,并预测流程中会发生什么,因为它可以在大范围内准确监测电流、电压和功率。该电机管理系统也是一个灵活的系统,支持六种通信协议,即Modbus™, CANopen,DeviceNet™, Profibus™, 以太网/IP和Modbus/TCP。TeSys T电机管理系统由几个组件组成,包括LTMR控制器、扩展模块、HMI和软件以及几个附件。LTMR控制器是管理基本功能的系统的主要组件。这包括对接地电流、电机温度、电机三相电流的测量,控制器还包括用于故障管理的逻辑输入和输出

      Main
      Range TeSys
      Product name TeSys T
      device short name LTMR
      Product or component type Motor controller
      Device application Equipment monitoring and control
      Measurement current 5…100 A
      [Us] rated supply voltage 100...240 V AC 50/60 Hz
      Current consumption 8...62.8 mA
      Supply voltage limits 93.5…264 V AC
      Communication port protocol CANopen
      Bus type CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, SUB-D 9 with 4 twisted shielded pairs cable
      CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, terminal block with 4 twisted shielded pairs cable

      Complementary
      [Ui] rated insulation voltage 690 V conforming to EN/IEC 60947-1
      690 V conforming to CSA C22.2 No 14
      690 V conforming to UL 508
      [Uimp] rated impulse withstand voltage 4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
      6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
      0.8 kV communication circuit conforming to EN/IEC 60947-4-1
      Short-circuit withstand 100 kA conforming to EN/IEC 60947-4-1
      Associated fuse rating 4 A gG for output
      0.5 A gG for control circuit
      Protection type Thermal protection
      Locked rotor
      Phase failure
      Earth-leakage protection
      Overload (long time)
      Power factor variation
      Phase unbalance
      Load fluctuation
      Thermal overload protection
      Reverse polarity protection
      Overload
      Network and machine diagnosis type Event recording
      Trip history information
      Starting current and time
      Running hours counter/operating time
      Motor control command recording
      Remaining operating time before overload tripping
      Fault recording
      Phase fault and earth fault trip counters
      Waiting time after overload tripping
      Trip context information
      Logic input number 6
      Input current 3.1 mA at 100 V
      7.5 mA at 240 V
      Current state 0 guaranteed Logic input: 0...40 V and <= 15 mA for 25 ms
      Current state 1 guaranteed Logic input: 79...264 V and >= 2 mA for 25 ms
      maximum output switching frequency 2 Hz
      Load current 5 A at 250 V AC for logic output
      5 A at 30 V DC for logic output
      Permissible power 480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
      30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
      maximum operating rate 1800 cyc/h
      Contacts type and composition 1 NO + 1 NC fault signal
      3 NO
      Metering type Earth-fault current
      Phase current I1, I2, I3 RMS
      Imbalance current
      Temperature
      Average current Iavg
      Measurement accuracy 5...15 % earth fault current internal measurement
      1 % voltage (100...830 V)
      3 % power factor
      5 % earth fault current external measurement
      +/- 30 min/year internal clock
      0,02 temperature
      5 % active and reactive power
      0,02 current
      Overvoltage category III
      Connection pitch 5.08 mm




    Baidu